Use
DL - 30 series of current relays for motor, transformer and transmission line overload and short-circuit protection circuit, as the starting element.
Main technical data
Error of motion: | The error of each setting is not greater than 6%; |
Return coefficient: | Not less than 0.8; |
Action time: | When the action value of 1.1 times, the action time is no more than 0.12s; |
Contact capacity: | When the voltage is not greater than 250V and current less than 2a, contacts disconnect power, this 50W 5 + 0.75ms time constant inductance load DC circuit with, in AC circuit for 250VA. |
Power consumption: | The minimum setting value, the relay coil power consumption does not exceed 20VA. |
Type number
|
The maximum Constant current |
Rated current
|
Long term current
|
Current setting Range |
Action current
|
|||
Coil series
|
Coil parallel
|
Coil series
|
Coil parallel
|
Coil series
|
Coil parallel
|
|||
DL—31
DL—32 DL—33 DL—34 |
0.0049A
|
Only a point of scale
|
0.00245A
|
0.0049A
|
||||
0.0064A
|
Only a point of scale
|
0.0032A
|
0.0064A
|
|||||
0.01A
|
0.02A
|
0.04A
|
0.02A
|
0.04A
|
0.0025~0.01A
|
0.0025~0.005A
|
0.005~0.01
|
|
0.05A
|
0.08A
|
0.16A
|
0.08A
|
0.16A
|
0.0125~0.05A
|
0.0125~0.025A
|
0.025~0.05A
|
|
0.2A
|
0.3A
|
0.6A
|
0.3A
|
0.6A
|
0.05~0.2A
|
0.05~0.1A
|
0.1~0.2A
|
|
0.6A
|
1A
|
2A
|
1A
|
2A
|
0.15~0.6A
|
0.15~0.3A
|
0.3~.6A
|
|
2A
|
3A
|
6A
|
4A
|
8A
|
0.5~2A
|
0.5~1A
|
1~2A
|
|
6A
|
6A
|
12A
|
6A
|
12A
|
1.5~6A
|
1.5~3A
|
3~6A
|
|
10A
|
10A
|
20A
|
10A
|
20A
|
2.5~10A
|
2.5~5A
|
5~10A
|
|
15A
|
10A
|
20A
|
15A
|
30A
|
3.75~15A
|
3.75~7.5A
|
7.5~15A
|
|
20A
|
10A
|
20A
|
15A
|
30A
|
5~10A
|
5~10A
|
10~20A
|
|
50A
|
15A
|
30A
|
20A
|
40A
|
12.5~25A
|
12.5~25A
|
25~50A
|
|
100A
|
15 |
30A
|
20A
|
40A
|
25~50A
|
25~50A
|
50~100A
|
|
200A
|
15A
|
30A
|
20A
|
40A
|
50~100A
|
50~100A
|
100~200A
|