Use
Ll - 10 series overcurrent relay (hereinafter referred to as the relay) used in AC power system for electric motor and transformer and transmission line over load and short-circuit protection.
Main technical data:
Type number
|
Rated current
|
Setting value
|
||
Rated current (A)
|
Action time (s)
|
Transient current multiple
|
||
LL-11/5
LL-11-1 |
5
|
2、2.5、3、3.5、4、4.5、5
|
0.5~4
|
对于LL-11~14
2~8 对于LL-11-1 ~-14-1 4-2 |
LL-11/10
LL-11-1 |
10
|
4、5、6、7、8、9、10
|
||
LL-12/5
LL-12-1 |
5
|
2、2.5、3、3.5、4、4.5、5
|
2~6
|
|
LL-12/10
LL-12-1 |
10
|
4、5、6、7、8、9、10
|
||
LL-13/5
LL-13-1 |
5
|
2、2.5、3、3.5、4、4.5、5
|
2~4
|
|
LL-13/10
LL-13-1 |
10
|
4、5、6、7、8、9、10
|
||
LL-14/5
LL-14-1 |
5
|
2、2.5、3、3.5、4、4.5、5
|
8~6
|
|
LL-14/10
LL-14-1 |
10
|
4、5、6、7、8、9、10
|
Note: special specifications ll - 10 - 1 (11 - 1, 12, 1, 13 - 1, 14 - 1) instantaneous current multiple 4 ~ 12, and other parameters and ll - 10 series corresponding
The current relay coil to allow long-term by 110% rated current;
Return coefficient: the maximum current and operating current to start contacts QJ to return to the original position of the ratio of not less than 0.85.
Power consumption: when the current action current relay setting value is not greater than 10VA.
Internal wiring diagram