Use
The DJ - 100 series voltage relay (hereinafter referred to as electromagnetic relay), instantaneous voltage relay.Widely used in the two loop line protection in power system, as a low voltage starting element and overvoltage protection.
Main technical parameters
|
Action time:
|
Over voltage relay at 1.1 times the actual action value, the action time is not more than 0.12s
Low voltage relay at 0.5 times the actual action value, the action time is not more than 0.15s.
|
Contact capacity:
|
No more than 250V voltage, the electric current does not exceed 5a, the time constant for 5 + 0.75ms DC sense circuit load, product output contact breaking capacity is 50W. The output contacts in the above specified load conditions, the product can act reliably and return 5 * 104 times. The output contact allows for a long time 5A.
|
Medium strength:
|
In the products of each conductive terminal even together, on the exposed uncharged metal part or between the shell, bear 2000V (RMS) 50Hz AC voltage which lasted 1 minute test without dielectric breakdown or flashover phenomenon.
|
|
Type number
|
Setting range
|
Long term permissible voltage
|
Contact specification
|
Return coefficient
|
Power consumption (minimum setting voltage)
|
Note
|
Coil series
|
Coil parallel
|
Moving
|
Dynamic break
|
DJ-111
|
15-60
50-200
100-400
|
70
220
440
|
35
110
220
|
1
|
|
≥0.8
|
≤1
|
|
DJ-121
|
15-60
50-200
100-400
|
70
220
440
|
35
110
220
|
|
1
|
DJ-131
|
15-60
50-200
100-400
|
70
220
440
|
35
110
220
|
1
|
1
|
DJ-131/60C
DJ-131/60CN
|
15-60
|
220
|
110
|
1
|
1
|
≤1.25
|
DJ-112
|
12-48
40-160
80-320
|
70
220
440
|
35
110
220
|
1
|
|
≤1.25
|
≤1
|
|
DJ-122
|
12-48
40-160
80-320
|
70
220
440
|
35
110
220
|
|
1
|
DJ-132
|
12-48
40-160
80-320
|
70
220
440
|
35
110
220
|
1
|
1
|
|