Use
Improved the relay JCDY - 2 DC voltage relay, not only has the characteristics of the original relay, set over voltage protection, under voltage lockout in one, can be widely used in DC screen, nickel cadmium battery screen, DC system working state monitoring automatic adjustment of the measuring element.
The main technical parameters
|
Rated DC voltage: | 220V、110V、48V |
Return coefficient: | 过压97-99%;欠压101-103%; |
The action time: | 1.1 times the action value under the action time is not more than 25ms; |
Return time: | 1.1 times the action value return time is not more than 25ms |
Setting error: | Not greater than + 2%. |
Power consumption: | Not is bigger than 10W. |
Contact capacity: | No more than 250V voltage, the electric current does not exceed 5a, the time constant for 5 + 0.75ms DC sense of load, the product output contact breaking capacity is 50W. The output contacts in the above specified load conditions, the product can act reliably and return 5 * 104 times. The output current is 5A connected to allow long-term contact. |
Internal wiring diagram
The appearance and installation size